Chapter 5 (Part 2): Degree of Freedom Analysis and Description Rule for a Single-Stage Flash Process
Conventional Approach to
the Degree of Freedom Analysis
Consider again the 5 component single-stage
flash process described in Part 1 of this chapter where all the variables associated with the feed steam
are assumed to be known. To illustrate that there are several approaches to listing the variables and
independent equations for the fully defined process, consider the case where for any stream only 4 mole fractions are considered as
variables (in which case the equation stating that the mole fractions sum to unity cannot be used as an equation),
and also where the vapor and liquid flow rates (V and L) are considered as variables (instead of the ratio V/L). In
this case the variables that apply can be listed as follows:
4 mole fractions in the liquid product
4 mole fractions in the vapor product
The vapor product flow rate
The liquid product flow rate
Temperature in the flash chamber
Pressure in the flash chamber
The amount of heat transferred in the heat exchanger
These variables can be solved
for using the following set of independent equations
5 phase equilibrium equations (one for each component)
Four species material balances
One overall material balance
One enthalpy balance
Since there are 13 variables and
11 equations given above, it follows that two of the variables listed above (for example temperature
and pressure or pressure and the heat transferred in the heat exchanger) must be assigned known values so
that the remaining 11 variables can be solved for using the 11 equations described above. Consequently there
are two degrees of freedom for this system. More generally, provided that the variables associated
with the feed are fixed, there will be 2 degrees of freedom for a single stage flash process regardless of the number of components
present since the specific number of components cancels out from the degree of freedom analysis. Note also that the determination of
the degrees of freedom just given is described by the following figure:
Fig. 1. The conventional approach to the degree of
freedom analysis.
Using the Description Rule to
Determine the Number of Degrees of Freedom
Although the method just described and illustrated
in Fig. 1 gives
the proper number of degrees of freedom, the task of listing the variables and equations is
prone to errors, especially since there is not a unique list of variables or a unique
list of equations for any given problem. This can be seen by comparing the list of variables and equations in the
above approach with that in the approach in
Part 1 of this chapter for the single-stage flash problem. It is worthwhile therefore to explore the use of a more
practical approach which
takes the viewpoint of the process unit builder and operator.
Consider again the case of a 5 component
single-stage flash process where all the variables associated with the feed have known values, and where
the following process flow diagram therefore applies:
Fig. 2. Adding control loops
to ensure steady state operation.
The left side of the above figure
shows the process for the case where manual control applies (except for the completely specified feed stream
where a flow control loop is present).
Clearly, the three manual valves shown must be given specific settings to achieve steady state operation, and
for random settings of these valves it is likely that the inventory of liquid in the flash chamber will either
be increasing or descreasing with time (so that steady state is not achieved). In practice, automatic control loops need
to be added to ensure steady state operation, as shown in the right side of the above figure where a pressure
control loop, a temperature control loop, and a liquid level control loop have been added.
When steady state
has been reached for the situation on the right side of the above figure, the number of equations that apply must
be equal to the number of variables that can be solved for so that the steady state values of the variables
can be solved for. Furthermore, for each control
loop that has been added to ensure steady state operation, a corresponding control equation has been added to
the system of governing equations, and possibly a new
variable (i.e., the controlled variable of the control loop) has also been added depending on
how the control loop operates. Therefore, by determining the number
of control loops that need to be added to
the system and then subtracting from this number the number of new variables (if any) added by the control loops, the degrees of freedom for the original
original system can be determined. The Description Rule calculation method therefore corresponds to Fig. 3 shown below,
which can be compared to the Fig. 1 shown above.
Fig. 3. The description rule approach
to the degree of freedom analysis.
As shown in the figures above, three control loops
are needed to ensure steady state operation (again assuming the feed stream variables are known), but one
of these control loops (the liquid level control system) does not affect the steady state values of
the variables being considered except for the liquid level itself, which is not a variable of interest here. This
indicates that the degrees of freedom
for the original system is 2. This result agrees that given above when the total numbers of equations and variables were
considered. Notice that in the description rule approach to the degree of freedom analysis no attempted is made to
list the entire set of variables and equations so that no attempt is made to determine I or D + E + F in Fig. 3.
In most cases the number of
control loops which must be added to the system to achieve steady state can be easily obtained by noting the number of control
loop actuators present in the system since every control loop must have an actuator, and all potential actuators in the system need
to be part of a control loop. The most common control loop actuator is a valve, and as a general rule a valve must
be present on every exit stream from the process as well as on each each steam line entering the system. Note that a special valve
termed a steam trap (as shown the second figure above) is generally located on the condensate line from a steam heater. Steam traps operate automatically
to ensure only condensed liquid exits a steam heating system, and consequently a steam trap cannot be an element in
a control loop. Note also that tanks containing two phases, such as the tank containing liquid and vapor in this example,
require a level control loop of some type to ensure that steady state is achieved.
Selection of Specified Variables to Completely Define a Problem
Note that although the above development indicates that temperature and pressure
specifically need to be specified for the single state flash process to become a completely specified problem, the key conclusion is that
there are two degrees of freedom for the problem as stated such that any two variables can be given fixed values to completely specify the problem. However, not all
possible pairs of variables, when specified, will yield a problem that can be solved. For example, if the mole fractions of two different
components are arbitrarily specified in the liquid phase, it may be that no solution is possible for the overall system of equations.
Alternatively, if the vapor product flow rate is specified at an arbitrary value to use one of the degrees of freedom available, then it is not
possible to arbitrarily select the liquid product flow rate (i.e., to use the liquid product flow rate as the second degree of freedom
available) since with the feed flow rate specified there is only one possibly liquid product flow rate possible is the vapor product
flow rate is specified.
Consideration of Construction Variables
In addition to the controlled variables described aove, in many cases
construction variables also need to be specified
in order to have a fully defined process. In the above example, the dimensions of the flash chamber and the heat exchanger
area can be considered contruction variables. However, in the case considered here these construction variables do
not affect the steady state values of the other variables beind considered, and therefore there are no construction variables that
need to be considered in the present case.
-
Description rule for a single stage flash. This material, which comes from Chapter 2 of
“Separation Processes” by C. J. King, describes a simple method to determine the number of
degrees of freedom for a single stage flash process.